HotLoop Transmitter puts a PLC’s values on the network as OPC UA PubSub, the way Part 14 of the OPC UA spec says to, from a library you drop into the CODESYS project. It is a transmitter in the instrument-loop sense: the part that puts the process value on the wire so something else can read it.

It is written in Structured Text over SysSocket UDP, and it needs no other library, no extra license, and no configurator. You add the library, call one function block once per cycle, and a UADP NetworkMessage goes out every publishing interval to a unicast address or a multicast group.

What that means for you: a PLC that has no PubSub library can still feed anything that subscribes to OPC UA PubSub, including HotLoop itself, with a few lines of Structured Text. Every message carries a timestamp from the PLC’s clock unless you switch it off with bTimestamp.

Every new HotLoop tool is written in Go unless there is a real reason. This is the real reason: the thing has to run inside the PLC’s own scan, in the IEC 61131-3 runtime, as a library the programmer references from their project. A CODESYS runtime runs Structured Text, not Go. The tests and tools around the library (the capture tool, the verifier) are Go.

  1. Install HotLoopTransmitter-1.1.0.library into the CODESYS library repository (Tools, Library Repository, Install), or install HotLoopTransmitter-1.1.0.package with the CODESYS Installer, then add it to the project’s Library Manager. The install page has the downloads and the details.
  2. Declare a publisher, add the variables you want to publish once at start, and call it every cycle:
PROGRAM PLC_PRG
VAR
pub : HLTX.FB_HLTX_Publisher;
bInit : BOOL;
END_VAR
IF NOT bInit THEN
bInit := TRUE;
pub.sDestination := '239.0.0.22'; // a unicast host or a multicast group
pub.uiPort := 4840;
pub.uiPublisherId := 1;
pub.uiWriterGroupId := 1;
pub.uiDataSetWriterId := 1;
pub.tPublishingInterval := T#100MS;
pub.AddReal(ADR(GVL.rTemperature));
pub.AddBool(ADR(GVL.bRunning));
pub.AddArray(ADR(GVL.aValues), HLTX.E_HLTX_Type.REAL_T, 250);
END_IF
pub.bEnable := TRUE;
pub();

The API page lists every input, output and method. The wire format page is the packet, byte by byte, with the sections of the spec that define each byte.

  • It never blocks. The socket is non-blocking and the message is built in a fixed buffer.
  • The cost of a call is the cost of building one message, and it is only paid on the cycles where a message goes out. Measured on a 20 ms task with two publishers and timestamps on: about 9.6 us added per cycle on average, 10 to 100 us on the cycles that send, and the longest cycle in the run 81 us. A busy host has stretched a single send to milliseconds. The measured numbers and their limits are in the timing page.
  • A socket error, a bad address or an oversized field list never faults the application. The block reports an eState and an eError, counts the failure, and the program keeps scanning.
  • It does not fragment. A message is at most 1472 bytes. A field list that does not fit puts the block in ConfigError and sends nothing.

The CODESYS Control for Linux SL 4.22.0.0 runtime, in a container. See the timing page and the proof page for what was run and what was read back. Not run on physical hardware.

HotLoop’s Business Source License 1.1, the same as every HotLoop product. The license page has the text.